- Condition
- CE 4.1: Missing or Inadequate Fire Stopping
- Article Type
- Common Element
- Article Number
- 4.1
- Warranty Year(s)
- Two Year
- Performance
Fire stopping shall be installed in accordance with the Ontario Building Code and the design.
- Warranty
One – Year – Work and Materials. Two-Year - Ontario Building Code Health and Safety Violation. Damage resulting from improper maintenance or additions, deletions or alterations made by the homeowner is excluded from the statutory warranty.
- Action
Fire stopping not installed in accordance with the Ontario Building Code or the design shall be repaired.
- Condition
- CE 4.2: Improperly Constructed Fire Seperations
- Article Type
- Common Element
- Article Number
- 4.2
- Warranty Year(s)
- One Year
- Performance
Fire separations should be constructed to meet the requirements of the Ontario Building Code and the design.
- Warranty
One-Year - Work and Materials. Two-Year - Ontario Building Code Health and Safety Violation.
- Action
Fire separations not meeting the acceptable condition shall be repaired.
- Condition
- CE 4.3: Unsealed Drywall Joints In Fire Seperations
- Article Type
- Common Element
- Article Number
- 4.3
- Warranty Year(s)
- One Year
- Performance
Partition is constructed to meet the requirements of the Ontario Building Code and the design.
- Warranty
One-Year - Work and Materials. Two-Year - Ontario Building Code Health and Safety Violation. Damage resulting from improper maintenance or additions, deletions or alterations made by the homeowner is excluded from the statutory warranty.
- Action
Partitions not meeting the acceptable Performance shall be repaired.
- Condition
- CE 6.1: Inadequate Operating Speed And/Or Acceleration
- Article Type
- Common Element
- Article Number
- 6.1
- Warranty Year(s)
- One Year
- Performance
All elevators in a bank shall operate within the same performance range and meet the performance criteria of the building design
- Warranty
One-Year - Work and Materials
- Action
Equipment not meeting the Acceptable Performance/Condition shall be repaired.
- Condition
- CE 6.2: Door Closing Too Quickly or Too Slowly
- Article Type
- Common Element
- Article Number
- 6.2
- Warranty Year(s)
- One Year
- Performance
Elevator doors shall operate within the manufacturer’s recommended speed ranges and shall not exceed the code limit for maximum allowable kinetic energy. Kinetic energy of a closing door shall be based upon the sum of the hoist-way and the car door weights as well as the weight of parts rigidly connected to the doors and shall also include the rotational inertia effects of the door operator and the connecting transmission. The door closing force necessary to prevent closing of the hoist-way door (or the car door or gate if power operated) from rest shall not exceed 135 N (30 lb.). This force shall be measured on the leading edge of the door with the door at any point between one-third and two-thirds of its travel, and shall also not exceed the maximum allowed code limits.
- Warranty
One-Year - Work and Materials
- Action
Equipment not meeting the Acceptable Performance/Condition shall be repaired.
- Condition
- CE 6.3: Elevator Cab Poorly Aligned
- Article Type
- Common Element
- Article Number
- 6.3
- Warranty Year(s)
- One Year
- Performance
- The maximum clearance between the elevator cab sill and the landing sill shall be not more than 32mm (1.25 in.). The distance must be uniform and consistent across the length of the sill.
- Warranty
- One-Year - Work and Materials
- Action
- Equipment not meeting the Acceptable Performance/Condition shall be repaired.
- Condition
- CE 6.4: Gaurds Missing On Elevator Equipment
- Article Type
- Common Element
- Article Number
- 6.4
- Warranty Year(s)
- One Year
- Performance
- Guards on elevator equipment will be provided as required by the TSSA regulations in force at the time of registration. Equipment shall not present a risk of entanglement, pinching, shearing, crushing, abrasion, electrical shock or tripping. The machine guarding must be provided with certification by a Professional Engineer indicating that the machine guarding is compliant with the MOL requirements. All machine guarding installations must be provided with an appropriate TSSA submission and must be performed by a licensed elevator contractor.
- Warranty
- One-Year - Work and Materials
- Action
- Equipment not meeting the Acceptable Performance/Condition shall be repaired.
- Condition
- CE 6.5: Guard Rails On Top Of Cabs
- Article Type
- Common Element
- Article Number
- 6.5
- Warranty Year(s)
- One Year
- Performance
- Guard rails on top of cabs will be provided as required by the TSSA regulations in force at the time of registration.
- Warranty
- One-Year - Work and Materials
- Action
- Guards not meeting the Acceptable Performance/Condition shall be repaired.
- Condition
- CE 6.6: Water In Pit
- Article Type
- Common Element
- Article Number
- 6.6
- Warranty Year(s)
- One Year
- Performance
- Elevator pits should be clear of standing water or fluids.
- Warranty
- One-Year - Work and Materials
- Action
- Pits not meeting the Acceptable Performance/Condition shall be repaired.
- Condition
- CE 6.7: Poor Elevator Levelling
- Article Type
- Common Element
- Article Number
- 6.7
- Warranty Year(s)
- One Year
- Performance
- Elevators shall stop and re-level as required by the design.
- Warranty
- One-Year - Work and Materials
- Action
- Equipment not meeting the Acceptable Performance/Condition shall be repaired.
- Condition
- CE 6.8: Construction Debris In Pit Or Elevator Machine Room
- Article Type
- Common Element
- Article Number
- 6.8
- Warranty Year(s)
- One Year
- Performance
After completion of construction, the pit, hoist-way equipment and elevator machine room should be cleaned to remove all construction debris, and to remove construction dust from elevator control equipment.
- Warranty
One-Year - Work and Materials
- Action
Equipment not meeting the Acceptable Performance/Condition shall be repaired.
- Condition
- CE 6.9: Elevator Not Conforming To Ontario Building Code Barrier Free Requirements
- Article Type
- Common Element
- Article Number
- 6.9
- Warranty Year(s)
- One Year
- Performance
Elevators shall conform to the requirements of the Ontario Building Code.
- Warranty
One-Year – Work and Materials. Two-Year – Health and Safety Violation of Ontario Building Code
- Action
Equipment not meeting the Acceptable Performance/Condition shall be repaired.
- Condition
- CE 6.10: Oil Leaks, Grease Fitting, Bearing Seals Shall Be Free Of Leaks Or Defect
- Article Type
- Common Element
- Article Number
- 6.10
- Warranty Year(s)
- One Year
- Performance
- Elevators equipped with oil fitting, packing, valves, pumps, reservoir tank (hydraulic elevators), or bearings (sealed or unsealed), deflector sheaves, sprockets, oil buffers, etc. shall be free of oil leaks or grease escaping or leaking from the fittings.
- Warranty
- One-Year - Work and Materials
- Action
- Equipment not meeting the Acceptable Performance/Condition shall be repaired.
- Condition
- CE 6.11: Electrical Schematics Missing
- Article Type
- Common Element
- Article Number
- 6.11
- Warranty Year(s)
- One Year
- Performance
All relevant schematics required for the proper maintenance and operation of the elevator shall be provided as required by the TSSA.
- Warranty
One-Year - Work and Materials
- Action
Equipment not meeting the Acceptable Performance/Condition shall be modified.
- Condition
- CE 6.12: Elevator Noise Due to Missing Or Inadequate Sound Mitigating Device(s)
- Article Type
- Common Element
- Article Number
- 6.12
- Warranty Year(s)
- One Year
- Performance
The elevators should be provided with appropriate sound mitigation devices as required by the design.
- Warranty
One-Year - Work and Materials
- Action
Equipment not meeting the Acceptable Performance/Condition shall be repaired.
- Condition
- CE 7.15: Equipment Cannot Be Maintained
- Article Type
- Common Element
- Article Number
- 7.15
- Warranty Year(s)
- One Year
- Performance
Equipment shall be installed in such a manner that it can be accessed for maintenance. Clearances shall be adequate to permit required maintenance.
- Warranty
One-Year - Work and Materials
- Action
Equipment not meeting the Acceptable Performance shall be relocated or modified.
- Condition
- CE 7.16: Missing Guards On Mechanical Equipment
- Article Type
- Common Element
- Article Number
- 7.16
- Warranty Year(s)
- One Year
- Performance
Equipment that includes moving parts that might cause pinching or entrapment shall be guarded.
- Warranty
One-Year - Work and Materials. Two-Year - Ontario Building Code Health and Safety Violations
- Action
Equipment not meeting the Acceptable Performance shall have guarding installed.
- Condition
- CE 7.17: Inadequate Air Supply
- Article Type
- Common Element
- Article Number
- 7.17
- Warranty Year(s)
- One Year
- Performance
Air supply systems shall provide the air flow required by the design.
- Warranty
One-Year - Work and Materials. Two-Year - Distribution and Delivery
- Action
Systems not meeting the Acceptable Performance shall be repaired.
- Condition
- CE 8.3: Electrical Equipment Missing Labels
- Article Type
- Common Element
- Article Number
- 8.3
- Warranty Year(s)
- One Year
- Performance
Electrical panels and circuits must be clearly labeled.
- Warranty
One-Year - Work and Materials
- Action
Missing labels must be provided.
Fire stopping is a rated assembly with particular dimensional and material requirements that must be adhered to.
Typically interior drywall joints are finished or sealed when constructed as part of a fire rated assembly. Joint treatment may vary depending on the specified assembly.
Typically, elevator consultants and elevator contractors’ engineers assist the architects and building owners with the selection of the number of elevators and escalators. The selection is based on the speed, performance criteria and times. Hence, the performance of the physical devices has to meet the standard performance criteria of the design in order to provide acceptable service. Alternatively, it may be possible for the elevator contractor to demonstrate that the actual performance of the elevators can meet the traffic handling capacity of the building.
Dust in elevator or escalator controls can lead to overheating, intermittent failures, poor lubrication, seizure of components and difficulties in troubleshooting
Barrier free design is covered by Appendix E of the Elevator Code. Under the terms of the Elevator Code, Appendix E is voluntary. However, Appendix E is a mandatory requirement under the Ontario Building Code, so full compliance to the referenced code is required. The following barrier-free requirements including appropriate height buttons Braille on buttons, position indicator, hands-free phones, call registration chime, passing floor chime, hall door jamb Braille, and voice annunciation indicating floor level may be affected.
A proper as-built elevator electrical diagram is required by the TSSA and is important for the safe operation of the elevators and escalators. Hence, it is critical for the longevity of the device to have an as-built diagram in plasticized covering.
This section does not relate to noise created by components not directly related to the elevators and does not consider noise transmission unless it is 10dBA greater than ambient. Sound mitigating devices may include isolation pads, electrical isolation filters, hydraulic mufflers, pipe isolation coupling or cushioning pads as required by the design.
In some instances specialized equipment may be needed to access some equipment for maintenance; this is not warranted.
Typically a balancing report is used to demonstrate that a system meets design requirements.