CE 2.1: Exposed Balcony Concrete Finishes Have Construction-Related Markings Such as Rust Stains, Chalkmarks, Embedded Nails
Article Type
Common Element
Article Number
2.1
Warranty Year(s)
One Year
Performance

Balcony finishes should be free of left-over materials and markings from construction.

Warranty

One-Year - Work and Materials

Action

Remnants from construction shall be removed. Minor surface imprints from formwork are acceptable.

Condition
CE 2.2: Exposed Balcony Concrete Finishes have Excessive Variation in Colour
Article Type
Common Element
Article Number
2.2
Warranty Year(s)
One Year
Performance

Variations in concrete colour are to be expected with cast-concrete construction. Variations are considered acceptable if the finishes provide a general uniformity in appearance when viewed from grade.

Warranty

One-Year - Work and Materials

Action

Concrete with excessive variation in colour shall be cleaned or coated to provide a uniform finish.

Condition
CE 2.3: Exposed Balcony Concrete Finishes Have Formwork Ridges
Article Type
Common Element
Article Number
2.3
Warranty Year(s)
One Year
Performance

There should be no formwork ridges on exposed balcony concrete surfaces.

Warranty

One-Year - Work and Materials

Action

Formwork ridges shall be smoothed.

Condition
CE 2.4: Corrosion Of Coated Metal Elements
Article Type
Common Element
Article Number
2.4
Warranty Year(s)
One Year
Performance

Protective coatings shall remain intact and effective for the warranty period. Protective coatings shall remain free of corrosion.

Warranty

One-Year - Work and Materials

Action

Corroded materials, corrosion shall be removed and the substrate refinished with appropriate protective coating.

Condition
CE 2.5: Defective Caulking
Article Type
Common Element
Article Number
2.5
Warranty Year(s)
One Year
Performance

Caulking should be installed in accordance with manufacturer’s specifications. Caulking shall remain intact without de-bonding, cracking/splitting or showing other signs of premature strain within the warranty period. Profiling of caulking should accommodate anticipated movement at the sealed joint. Caulking must cure as anticipated in the manufacturer’s specifications. All joints shown in the design to be caulked shall be caulked.

Warranty

One-Year - Work and Materials. One-Year – Ontario Building Code Violation. Two-Year – Cladding Detachment, Displacement or Deterioration. Damage resulting from improper maintenance is not covered by the statutory warranty

Action

Caulking which does not achieve the specified performance requirements shall be repaired.

Condition
CE 2.6: Water Collects on Window or Door Sills or Flashings
Article Type
Common Element
Article Number
2.6
Warranty Year(s)
One Year
Performance

Window and door sills and related flashings designed to control surface water shall not collect water.

Warranty

One-Year - Work and Materials

Action

Window sills and flashings not meeting the acceptable performance shall be corrected.

Condition
CE 2.7: Drip Edges Do Not Shed Water Away From Wall Elements
Article Type
Common Element
Article Number
2.7
Warranty Year(s)
One Year
Performance

Drip edges shall shed water away from adjacent cladding elements and shall not concentrate water run-off onto the cladding unless so intended by the design.

Warranty

One-Year - Work and Materials

Action

Where drip edges are provided, they must be effective

Condition
CE 2.8: Efflorescence On Masonry Surfaces
Article Type
Common Element
Article Number
2.8
Warranty Year(s)
One Year
Performance

Efflorescence commonly occurs on masonry and of itself is normal and not warranted. Concentrations of efflorescence that persist over time may indicate an underlying concern that may have warranty coverage.

Warranty

One-Year-Work and Materials

Action

If it is determined that a defect in work or material is the cause of the efflorescence, repairs to the defect shall be made.

Condition
CE 2.9: Efflorescence Icicle or Ice Damming Formation
Article Type
Common Element
Article Number
2.9
Warranty Year(s)
One Year
Performance

Attics should be provided with sufficient ventilation (if designed to include ventilation), air sealing and thermal insulation, and roofs should have adequate eaves protection to minimize ice damming and icicle formation.

Warranty

One-Year - Work and Materials

Action

Where icicle or ice damming development can be related to a defect in the attic ventilation, eaves protection, thermal insulation, and air leakage from the interior or other workmanship-related concerns, the defects shall be corrected to minimize ice build-up.

Condition
CE 2.10: Damaged Precast Concrete and Other Prefabricated Claddings
Article Type
Common Element
Article Number
2.10
Warranty Year(s)
One Year
Performance

Precast concrete panels and other prefabricated cladding components should be intact without aesthetic damage visible from a distance of 6 m and with no missing sections. Damage to the panel should not detract from the architectural intent.

Warranty

One-Year - Work and Materials

Action

Damaged panels shall be repaired.

Condition
CE 2.11: Precast Concrete Cracking
Article Type
Common Element
Article Number
2.11
Warranty Year(s)
One Year
Performance

There shall be no cracks that penetrate through the full depth of a precast concrete panel.

Warranty

One-Year - Work and Materials

Action

The vendor/builder shall obtain expert advice considering the structural and building envelope implications of the cracking to determine if remedial action is required. The identified actions must be completed.

Condition
CE 2.12: Deteriorating Masonry Cladding
Article Type
Common Element
Article Number
2.12
Warranty Year(s)
One Year
Performance

Masonry cladding shall be manufactured and installed to prevent premature deterioration.

Warranty

One-Year – Work and Materials. Two -Year – Cladding Detachment, Displacement or Deterioration. Damage resulting from normal wear and tear, improper maintenance or additions, alterations and deletions made by the homeowner is not covered by the statutory warranty.

Action

Masonry cladding that is deteriorated, detached, or displaced shall be repaired.

Condition
CE 2.13: Cracks in Exterior Stucco Wall Surfaces
Article Type
Common Element
Article Number
2.13
Performance

Fine hairline cracks that do not negatively affect the performance of the stucco are acceptable.

Warranty

One - Year – Work and Materials. One - Year – Ontario Building Code Violations. Two -Year – Cladding Detachment, Displacement or Deterioration. Damage resulting from normal wear and tear, improper maintenance or additions, alterations and deletions made by the homeowner is not covered by the statutory warranty.

Action

Stucco finish not meeting the acceptable condition shall be repaired.

Condition
CE 2.14: EIFS Cracking
Article Type
Common Element
Article Number
2.14
Warranty Year(s)
One Year
Performance

Surfaces shall be generally free of cracks.

Warranty

One-Year - Work and Materials. Damage resulting from normal wear and tear, improper maintenance or additions, alterations and deletions made by the homeowner is not covered by the statutory warranty.

Action

Cracks not meeting the acceptable performance requirements must be repaired. Repairs must meet the requirements of the system manufacturer. Every reasonable attempt should be made to match the finishes.

Condition
CE 2.15: Exterior Paint/Coating is Peeling or Bubbling
Article Type
Common Element
Article Number
2.15
Performance

Paint or coating on cladding shall not separate from the substrate.

Warranty

One - Year – Work and Materials. One - Year – Ontario Building Code Violations. Damage resulting from normal wear and tear, improper maintenance or additions, alterations and deletions made by the homeowner is not covered by the statutory warranty.

Action

Paint/coating not meeting the acceptable condition shall be repaired.

Condition
CE 2.16: Water Leak Through Building Envelope (Exterior Closure)
Article Type
Common Element
Article Number
2.16
Performance

The building envelope/exterior closure shall be constructed to prevent water entry into the interior of the building.

Warranty

One - Year – Work and Materials. One - Year – Ontario Building Code Violations. Two -Year – Building Envelope Water Penetration. Damage resulting from normal wear and tear, improper maintenance or additions, alterations and deletions made by the homeowner is not covered by the statutory warranty.

Action

Building envelopes/exterior closures not meeting the acceptable condition shall be repaired.

Condition
CE 2.21: Weep Holes Missing in Masonry Exterior Cavity Wall or Veneer System
Article Type
Common Element
Article Number
2.21
Performance

Weep holes in masonry veneer shall be installed to achieve the performance required by the Ontario Building Code.

Warranty

One --Year- Work and Materials. One – Year – Ontario Building Code Violation

Action

Masonry veneer not meeting the acceptable condition shall be repaired.

Condition
Common Element 2.22: Discontinuity In Air Barrier System
Article Type
Common Element
Article Number
2.22
Performance

The air barrier system shall meet the requirements of the Ontario Building Code.

Warranty

One – Year- Work and Materials. One – Year – Ontario Building Code Violation. Two – Year- Health and Safety. Damage resulting from improper maintenance or additions, deletions or alterations made by the homeowner is excluded from the statutory warranty.

Action

Air barrier systems not in accordance with the acceptable condition shall be repaired.

Condition
CE 2.23: Draft Felt At Electrical Outlet
Article Type
Common Element
Article Number
2.23
Warranty Year(s)
One Year
Performance

Electrical boxes on exterior walls that are installed in the plane of the air barrier system shall be installed to prevent air infiltration.

Warranty

One-Year - Work and Materials. Damage resulting from normal wear and tear, improper maintenance or additions, alterations and deletions made by the homeowner is not covered by the statutory warranty.

Action

Electrical boxes not meeting the acceptable condition shall be repaired.

Condition
CE 2.24: Movement Joints In Masonry Are Obstructed
Article Type
Common Element
Article Number
2.24
Warranty Year(s)
One Year
Performance

Movement joints in masonry construction shall allow free movement of masonry to prevent or relieve stress due to differential movement.

Warranty

One-Year - Work and Materials

Action

Movement joints not meeting the Acceptable Performance shall be repaired.

Condition
FH 3.8: Condensation Forming Between Insulating (Factory Sealed) Glass Unit
Article Type
Freehold
Article Number
3.8
Warranty Year(s)
One Year
Performance

Insulating glass units shall be free from condensation between the panes.

Warranty

One-Year - Work and Materials

Action

Insulating glass units with condensation between the panes shall be replaced.

Condition
FH 3.9: Exterior Door is Warped
Article Type
Freehold
Article Number
3.9
Warranty Year(s)
One Year
Performance

Doors shall not warp to the extent that they become inoperable or cease to be weather resistant. Doors between a home and an attached garage must be maintained to be gas-proof.

Warranty

One-Year - Work and Materials. Two-Year - Ontario Building Code Health & Safety Violation for doors requiring gas-proofing. • Damage resulting from improper maintenance or alterations, deletions or additions made by the homeowner is not covered by the statutory warranty.

Action

Doors not meeting the acceptable performance shall be replaced.

Condition
FH 3.10: Exterior Metal Door is Dented
Article Type
Freehold
Article Number
3.10
Warranty Year(s)
One Year
Performance

Exterior doors shall not be dented at the time of the PDI.

Warranty

One-Year - Work and Materials

Action

Dented exterior metal doors noted on the PDI Form shall be repaired. If not noted, the homeowner must establish that the damage was caused by the builder.

Condition
FH 3.11: Shrinkage Of Inserted Panels Shows Raw Wood Edges On Exterior Wood Doors
Article Type
Freehold
Article Number
3.11
Warranty Year(s)
One Year
Performance

Wooden panels will shrink and expand because of temperature and/or humidity changes, and may expose unpainted surfaces; this is acceptable. However, gaps between the edge of an inserted panel and the rest of the door caused by shrinkage are not normal and not acceptable.

Warranty

One-Year - Work and Materials. · Normal shrinkage of materials caused by drying after construction is not covered by the statutory warranty.

Action

Doors not meeting the acceptable condition shall be repaired.

Condition
FH 3.12: Cracks And Splits In Exterior Wood Doors
Article Type
Freehold
Article Number
3.12
Warranty Year(s)
One Year
Performance

Cracks penetrating through the door are not acceptable.

Warranty

One-Year - Work and Materials

Action

Doors not meeting the acceptable condition shall be repaired.

Condition
FH 3.13: Exterior Door Sticks
Article Type
Freehold
Article Number
3.13
Warranty Year(s)
One Year
Performance

Exterior doors and their hardware shall be installed to operate with minimal binding taking into account the weatherstripping seal and seasonal periods of high humidity.

Warranty

One-Year - Work and Materials. · Alterations, deletions and additions made by the homeowner are not covered by the statutory warranty.

Action

Doors and hardware not meeting the acceptable performance shall be repaired.

Condition
FH 3.14: Exterior Door Will Not Close Completely
Article Type
Freehold
Article Number
3.14
Warranty Year(s)
One Year
Performance

Exterior doors shall close completely and latch securely.

Warranty

One-Year - Work and Materials

Action

Doors not meeting the acceptable performance shall be repaired.

Condition
FH 3.15: Plastic Moulding On Exterior Door Is Deformed
Article Type
Freehold
Article Number
3.15
Warranty Year(s)
One Year
Performance

The plastic mouldings on exterior doors shall not deform when the door is installed in accordance with the manufacturer’s installation instructions.

Warranty

One-Year - Work and Materials. · Damage caused by improper maintenance or material, design or work supplied by the homeowner is not covered by the statutory warranty.

Action

Exterior doors not meeting the acceptable condition shall be repaired.

Condition
FH 3.16: Exterior Door Swings Open Or Closed By Itself
Article Type
Freehold
Article Number
3.16
Warranty Year(s)
One Year
Performance

Exterior doors shall be installed sufficiently plumb and square so they do not swing by themselves due to the force of gravity alone

Warranty

One-Year - Work and Materials. · Alterations, deletions or additions by the homeowner are not covered by the statutory warranty.

Action

Exterior doors not meeting the acceptable performance shall be repaired.

Condition
FH 3.17: Exterior Door Is Crooked In The Frame
Article Type
Freehold
Article Number
3.17
Warranty Year(s)
One Year
Performance

Exterior doors must have a proper weather seal when closed. The weatherstripping must contact the perimeter of the door.

Warranty

One-Year - Work and Materials. · Damage resulting from normal wear and tear or improper maintenance is not covered by the statutory warranty.

Action

Exterior doors not meeting the acceptable condition shall be repaired.

Condition
FH 3.18: Exterior Door Hardware Or Decorative Metal Trip Has Discoloured
Article Type
Freehold
Article Number
3.18
Performance

Finishes on door hardware and fixtures may discolour.

Warranty

None

Action

No action by the builder is required.

Condition
FH 4.19: Water Leakage at Doors and Windows or at the top of the foundation
Article Type
Freehold
Article Number
4.19
Warranty Year(s)
One Year
Performance

Openings in exterior walls such as windows and doors, and junctions between cladding materials, shall not allow water penetration.

Warranty

One-Year - Ontario Building Code Violations. Two-Year - Building Envelope Water Penetration. · Water penetration due to improper maintenance is excluded from the statutory warranty.

Action

Defects resulting in water penetration around windows, doors, and over the top of the foundation shall be repaired.

Condition
FH 8.2: Exterior Air Infiltration Through Windows and Doors
Article Type
Freehold
Article Number
8.2
Warranty Year(s)
One Year
Performance

Windows and doors shall meet the rating for weather tightness required by the Building Code.

Warranty

One-Year - Work and Materials

Action

Ensure the window or door has been tested to meet the required weather tightness rating. Adjust weather stripping and/or hardware to reduce air leakage by ensuring positive contact along the weather seal.

Remarks

Cast concrete will inherently have colour variations. While upgraded finishes are possible, they are not mandatory and are at the discretion of the design team. There are no requirements in the Ontario Building Code to paint the surface. However, if the builder does apply paint (of the appropriate type) to the surface the warranty shall apply to the installed paint.

Remarks

When the removal of marks or imperfections from the concrete forms is carried out, it must be carried out in a good workmanlike manner, and should not degrade the overall aesthetic appearance that was intended.

Remarks

This item is not intended to address corrosion related to chips or other post-installation damage, but rather material failure of the paint finish. Components which are specified to be shop primed will be expected to corrode, and corrosion of these elements is not warranted.

Remarks

Efflorescence is the formation of a white crystalline deposit on the surface of concrete and masonry when moisture evaporates from the surface. It is an indication that moisture is moving through the material to the surface.

Remarks

Icicle formation can pose a hazard to building users. Some regions are more susceptible to icicle formation than others. Where water, snow or ice can accumulate on a building, provision shall be made to minimize the likelihood of hazardous conditions arising from such accumulation.

Remarks

Precast concrete panels are often damaged during installation and require repair. Some damage may be acceptable without repair if located in service areas not accessed by residents or the general public, providing the damage does not impact the anchorage or permit water penetration. Damage occurring from owner-related activities e.g. window washing, is not covered by warranty.

Remarks

Some cracking which does not fully penetrate a panel may still be structurally significant and may require review.

Remarks

The colour/texture of repaired areas shall match the existing as closely as possible when dry. Variation in colour may be noticeable when wet. Where colour variation of the repaired area is visible under normal lighting and dry conditions from 6 m, the colour shall be adjusted. Professional tinting methods are acceptable to adjust colour. Masonry includes brick, block, stone, manufactured stone (or similar) and related materials Deterioration of masonry can result from problems with manufacture, installation or exposure.

Remarks

Stucco refers to systems typically over 6mm thick incorporating Portland cement. Cracks may be acceptable from a performance perspective if the system is drained, but may not be acceptable from an aesthetic perspective depending on the location of the cracks. Some cracking in areas of the building which are not routinely occupied (mechanical penthouse for example) may be considered acceptable if it does not negatively impact performance (leakage resistance etc). The colour or texture of repaired areas shall match the existing as close as possible, and the patched area should not be readily apparent when viewed from a distance of 6 m under normal lighting conditions. Generally the cracks which are intended to be repaired will be visible from a distance of 6m however, in some instances; smaller cracks may negatively impact performance. The width of cracks will vary with temperature. Larger in cold weather, smaller in hot weather.

Remarks

EIFS (exterior insulated finish systems) should be designed to minimize cracking through the use of control joints/limited panel sizes. ULC S716.1 Materials and Systems; ULC S716.2 Installation of EIFS Components and Water Restive Barriers; and ULC S716.3 Design Application provide guidance for the design and installation of EIFS. Some cracks may be acceptable from a performance perspective if the system is drained, but may not be acceptable from an aesthetic perspective depending on the location of the cracks. Some cracking in areas of the building which are not routinely occupied (mechanical penthouse for example) may be considered acceptable if it does not negatively impact performance (leakage resistance etc). The colour or texture of repaired areas shall match the existing as close as possible, and the patched area should not be readily apparent when viewed from a distance of 6 m under normal lighting conditions. Generally the cracks which are intended to be repaired will be visible from a distance of 6m however, in some instances; smaller cracks may negatively impact performance. The width of cracks will vary with temperature. Wider in cold weather, narrower in hot weather.

Remarks

Paint/coating includes any finish applied to a substrate whether factory-applied or site-applied Paint/coating separating from the substrate may indicate a problem with trapped moisture. The colour or texture of repaired areas shall match the existing as close as possible. The patched area should not be readily apparent when viewed from a distance of 6 m under normal lighting conditions.

Remarks

Leakage into the interior refers both to leakage into occupied spaces and also to leakage into the concealed portions of a wall system that is intended to be face-sealed. The building envelope/exterior closure includes the elements which separate the interior conditioned space from the exterior and includes cladding, windows, doors, vents, louvers, grilles etc. Roofing is covered separately. Joints and cracks in exterior wall surfaces and around openings shall be properly sealed to prevent the entry of water unless otherwise considered by the design. Repairs cannot alter the design intent of the cladding system. For example, leaks in a rain-screen system cannot be face-sealed.

Remarks

The Ontario Building Code references CSA A371 “Masonry Construction for Buildings”; section 12 discusses requirement for weep holes.

Remarks

Continuity of the air barrier is important to maintain acceptable conditions for building occupants to minimize the accumulation of condensation within the assemblies, to control heat transfer to roofs where ice damming occur and to allow proper operation of the building services.

Remarks

Some drafts may occur around electrical outlets or receptacles on exterior walls, particularly when it is cold or windy. Convection air movement may simulate draft conditions.

Remarks

The Ontario Building Code references CSA A371 “Masonry Construction for Buildings”

Remarks

Condensation between panes indicates the airtight seal around the edge of the glass is broken. An extended warranty may be available through the window manufacturer. See Also: 3.7 WINDOW UNIT LEAKS DURING RAIN 8.5 CONDENSATION AND/OR FROST ON WINDOWS

Remarks

Confirm proper operation of exterior doors during the PDI and record any malfunction on the PDI Form to avoid any dispute about whether the damage was caused by the builder. Exterior doors can warp to some degree due to temperature differential between inside and outside surfaces. Garage doors between the garage space and the outdoors are not required to be weatherstripped. See Also: 3.13 EXTERIOR DOOR STICKS 3.14 EXTERIOR DOOR WILL NOT CLOSE COMPLETELY 3.15 PLASTIC MOULDING ON EXTERIOR DOOR IS DEFORMED 3.17 EXTERIOR DOOR IS CROOKED IN THE FRAME

Remarks

Identify damaged doors on the PDI Form to avoid any dispute about whether the damage was caused by the builder. Filling the dent is an acceptable repair (e.g. spot putty).

Remarks

None

Remarks

None

Remarks

Confirm proper operation of exterior doors during the PDI and record any malfunction on the PDI Form to avoid any dispute about whether the damage was caused by the builder. Exterior doors can warp to some degree because of the difference in the temperature between inside and outside surfaces. See Also: 3.9 EXTERIOR DOOR IS WARPED 3.14 EXTERIOR DOOR WILL NOT CLOSE COMPLETELY 3.17 EXTERIOR DOOR IS CROOKED IN THE FRAME

Remarks

Confirm proper operation of exterior doors during the PDI and record any malfunction on the PDI Form to avoid any dispute about whether the damage was caused by the builder. Slight pressure may be required during latching to compress the weatherstripping. Exterior doors can warp to some degree because of the difference in the temperature between inside and outside surfaces. See Also: 3.9 EXTERIOR DOOR IS WARPED 3.13 EXTERIOR DOOR STICKS 3.17 EXTERIOR DOOR IS CROOKED IN THE FRAME

Remarks

Generally, exterior door manufacturers indicate storm doors are not to be installed over metal exterior doors. Heat buildup between a storm door and the exterior door can increase significantly, damaging any heat-susceptible parts such as plastic mouldings around a window insert or decorative surface-applied mouldings. The homeowner is also cautioned to follow manufacturer’s recommendations on maintenance and painting the mouldings a dark colour, with or without the use of a storm door; dark-coloured moulding is likely to deform and should be avoided.

Remarks

Confirm proper operation of exterior doors during the PDI and record any malfunction on the PDI Form to avoid any dispute about whether the damage was caused by the builder. Doors will swing open or closed by the force of gravity if the hinges are not aligned plumb. See Also: 3.9 EXTERIOR DOOR IS WARPED 3.17 EXTERIOR DOOR IS CROOKED IN THE FRAME

Remarks

Confirm proper operation of exterior doors during the PDI and record any malfunction on the PDI Form to avoid any dispute about whether the damage was caused by the builder. Variance in the width of the gap between the door and the frame is acceptable unless the proper operation of the door is affected. See Also: 3.9 EXTERIOR DOOR IS WARPED 3.13 EXTERIOR DOOR STICKS 3.14 EXTERIOR DOOR WILL NOT CLOSE COMPLETELY

Remarks

Some hardware may have a coating to inhibit discolouration. Maintaining protective coatings or removing discolouration is part of effective home maintenance. Oxidation and environmental pollutants can accelerate discolouration.

Remarks

Flashings must be installed above exterior wall openings and at the top of the foundation (masonry veneer) to direct water to the exterior. Perforations in flashing due to physical damage or chemical incompatibility, deterioration, improper termination and lack of weep holes in masonry veneer can allow water to drain to the interior. See Also: 1.13 FOUNDATION WALL LEAKS Appendix A5 “How to Conduct a Water Test”

Remarks

`